Panasonic Eco Solutions Nordic AB
MEW01623
Rev: -
SCI A <-> SCI 0 or SCI 0 <-> SCI B
...and so on.
If it is a single break (cut-off) on the loop there will be no other fault
messages.
If there are several breaks on the loop the message shows the last
isolator before the break in the A-direction (incl. the following
isolator). There will also be a "FAULT: No reply ....." message for
each unit that EBL128 cannot find and "FAULT: Several faults ...".
th
NOTE! Each 10
minute a new attempt is made to communicate in
the A-direction only.
When all breaks are repaired (corrected) the communication
automatically returns to communicate in the A-direction only.
FAULT: Earth fault (minus)
FAULT: Earth fault (plus)
Earth fault is detected. The system voltage is normally 24 V DC.
+24 V to earth is normally 12.5 V. 0 V to earth is normally 11.5 V.
Voltage to earth < 3.4 V = Earth fault (minus).
Voltage to earth > 18.3 V = Earth fault (plus).
Check all cables (for damage, etc.). The function cannot be
guaranteed. Call for service personnel/engineer.
FAULT: Earth fault, techn address xxx
This is valid for an external power supply (e.g. 3366) connected on the
COM loop. Check all cables connected to the unit.
FAULT: EPU x
EPU=1728. (Ext. Presentation Unit)
The unit is programmed as another type of unit than the SSD says or a
faulty unit.
FAULT: Expansion board x
Valid for the 8 zones exp. board 4580, the 8 relays exp. board 4581
and the Inputs and outputs exp. board 4583 mounted in the c.i.e.
(EBL128). Also valid for the I/O Matrix board 4582 connected on the
COM loop, i.e. mounted outside the c.i.e.
53
The fault has to be acknowledged and it can last up to 10 minutes before
the communication returns to communicate in the A-direction only.
60
EBL128 Operating Instructions V2.0.x
53