5
LED indicators on the Fire Brigade Panel (FBP)
LED indicator
L1
Fire (5 red)
Blinking (0.4/0.4s)
L2
Alarms queued (2 red)
Blinking (0.4/0.4s)
L3
Extinguishing (red)
L4
Ventilation (yellow)
L5
Fire brigade tx (red)
L6
Operation (green)

LED indicators and push buttons

LEDs and push buttons can vary according to configuration /
convention / country / language.
See also Figure 2, page 14.
Indicating
Fire alarm (also heavy smoke/heat alarm, Quiet alarm & key
3
cabinet alarm)
More than one unit / zone have generated fire alarm.
Output(s) activated for extinguishing equipment.
Output(s) activated for fire/smoke ventilation equipment.
Output activated for Fire brigade tx (routing equipment)
and/or corresponding programmable output(s) of type routing
4
equipment.
Test of routing equipment in progress (see menu H1).
Power on, i.e. EBL128 is power supplied via the rectifier or
the backup battery.
(FBP push buttons on next page)
3
In the New Zealand convention also "Acknowledged alarm" (ACK).
4
L3, L4 and L5 can as an alternative be programmed to indicate when a
programmable input is activated, i.e. input trigger condition "Extinguishing
system released", "Activated fire ventilation" and "Activated routing
equipment" respectively (e.g. L5 can be turned on when a programmable
input is activated by an activated routing equipment output). L5 is turned on
until all fire alarms are reset.
16