Panasonic Eco Solutions Nordic AB
MEW01623
Rev: -
Mark the required checkbox(es). Click "Start". Information will be
shown in the "Status" column and in the large white field. There is a
progress bar in the dialog box as well as in the EBL128display:
Download in progress......
▪▪▪▪▪▪▪▪
When the download is completed in a correct way, the following text
message will be shown:
Download completed successfully.
Control unit will now restart
Now, an automatic warm restart will take place (see chapter "Restart",
page 77) followed by a restart fault, code 25.
If the download was not completed or incorrect, the following text
message will be shown:
Checksum fault in downloaded data.
Control unit will now restart
Now, an automatic warm restart will take place (see chapter "Restart",
page 77.
After the restart another text message will be shown in the display:
FAULT: Site specific data (SSD)
Date: MM-DD
Time: HH:MM
This text message means that the SSD have not been downloaded
correctly, i.e. try to download the SSD once more.
73