Action
"Access"
Scroll to menu H5.
"A"
Scroll to menu A4
"A"
81
""
"Return"
"Return"
Rev: -
Display current consumption in unit
(H5/A4)
Control unit:
current at 24 V) for the control unit when it is connected to the mains
(230 V AC), i.e. this function is not working by battery backaup.
NOTE! No or very small current consumption will not be presented
correctly / precisely since the accuracy is ± 5 mA.
Charging: The battery charging current.
Low capacity voltage difference: During the battery capacity check
the voltage is measured with and without a resistor. A difference
between these two voltages > 2100 mV will result in a "Low battery
capacity" fault. This is checked every 4
Text in display
Service
Calibration of supervised outputs
Display current consumption in unit
Current consumption unit: XXXX mA
Charging: XXXX mA
Low capacity voltage diff: XXXXX mV
Display current consumption in unit
Service
NOTE! Each window is updated continuously.
81
This window will not be visible until 4 hours after the c.i.e. is powered and
the batteries have to be connected.
EBL128 Operating Instructions V2.0.x
The total current consumption (incl. the charging
th
ACCEPT? H5
ACCEPT? A1
ACCEPT? A4
ACCEPT? A4
ACCEPT? H5
117
hour.
Comments
According to chapter
"Access", see page 81.
""
Press
for the second
information window.
""
Press
for the first
information window.
Scroll or press "Return" to
H5.