Panasonic EBL128 Operating Instructions Manual page 86

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
The zone(s) will stay in test mode until the test mode is ended but after 60 minutes or if you press
"Return" two times, you will be logged out from menu H1.
Perform the test as quickly as possible, since the output(s) for routing equipment (fire brigade tx) are disabled
(also the parts of the zones in test mode, not visible for the test personnel, are disabled).
In order to shorten the testing time, any time delay for the detectors / zones in test mode will be "disabled",
i.e. fire alarm will be detected faster than normally.
In the tested alarm point, the LED will be lit about ten seconds until the alarm point is automatically reset.
A detector in test mode will not be able to activate fault.
After 60 minutes or
"Return"
"Return"
(When required:
"Access", "Password")
"A"
"A"
Some national regulations also require a routine test of the routing equipment. Press "A" for no test or press
"1" and "A" to start such a test. The following will happen:
 EBL128 "Fault tx" output will be de-activated
A 60 seconds count-down starts.
 After 30 seconds, EBL128 "Fire brigade tx" output (and corresponding programmable outputs type 4 =
routing equipment) will be activated as well, indicated by the LED "Fire brigade tx" (L15).
 After another 30 seconds, the test will be ended and all the outputs and LEDs will return to "normal".
"1", "A"
"A"
Rev: -
Zones 01 in test mode
NOTE! See chapter "The display in EBL128", page 21
regarding priority order.
Zones in test mode:
01
02
03
04
Test of routing equipment? 0
(1 = Yes, 0 = No)
Test of routing equipment in progress.
nn seconds left.
Monthly test is completed!
Perform monthly test
NOTE!
a) If an alarm point (e.g. a manual call point) is in alarm state when
the test mode is ended, there will be a fire alarm activated.
b) When the "Fire door closing" function is used, the fire door(s) will
be closed when the zone involved is set in test mode.
69
NOTE! This output is activated in normal state.
EBL128 Operating Instructions V2.0.x
More...
End test:
ACCEPT
ACCEPT
69
, indicated by the LED "Fault tx activated" (L11).
ACCEPT
ACCEPT? H1
84
You are no longer in menu
H1 but still in test mode.
Press "A" to end the test
mode.
The LED "Test mode" is
turned OFF.
"nn" starts at 60 and will
count down to 00.
Scroll or press "Return" to
log off.