Version: Menu H4/U7 can be used to see the EBL128 software /
firmware version.
Alarm counter The alarm counter is increased with "1" every time
the c.i.e. enters the real "fire alarm condition" (Fire alarm indication in
the display, LEDs "Fire" lit and the c.i.e. buzzer sounding), i.e. not for
zones in test mode. It starts on 000 and goes to 999. It can be reset to
000 via EBLWin (Control unit menu "Reset alarm counter..."). It is
stored in an EEPROM, i.e. the value will be retained also after the
c.i.e. has been de-energized.
Text in display
Present system status
Disablement
Version and alarm counter
Version: X.X.X
Alarm counter: yyy
Version and alarm counter
Present system status
EBL128 Operating Instructions V2.0.x
ACCEPT? H4
ACCEPT? U1
ACCEPT? U7
ACCEPT? U7
ACCEPT? H4
110
Comments
According to chapter
"Access", see page 81.
Press "A" to accept.
Press "Return" to menu
U7.
Scroll or press "Return"
to menu H4.
Scroll or press "Return".