Fault Acknowledge - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
Rev: -
18.2

Fault acknowledge

The LEDs "Fault tx activated" (L11) and "General fault" (L7) are
turned ON.
(LEDs Fault / Disablements "Alarm devices" (L13), "System fault"
(L14) and/or "Fire brigade tx" (L15) might be turned ON as well.)
Output for routing equipment (Fault tx) is activated.
Output for general fault is activated.
Output for general charge fault might be activated.
A fault message, date and time, is shown in the EBL128 display.
After the time might be shown
fault is generated.
After the time might be shown
"Serviced"
serviced / corrected.
are set (via EBLWin) to be "Not latched".
Login, according to chapter "Access", page 81.
Use menu H6 (access code for Building officer or Service
personnel is required) for fault acknowledge, see chapter "FAULT
Acknowledge (H6)", page 123. Menu H6 is a list showing up to
200 faults (not acknowledged faults and/or acknowledged but not
corrected faults). The first fault in the list is the most recent fault.
When a fault is both acknowledged and corrected it will be
removed from the list (and a new fault can be shown, if there are
more than 200). All fault events are shown in the event log (menu
H4/U6).
All faults have to be individually acknowledged one by one with
the yellow push button "Fault acknowledge" (P6). Use  or 
keys to scroll.
If a fault has been serviced / corrected before it has been
acknowledged, the text
still has to be acknowledged.
When a fault is corrected and acknowledged, it will disappear
from the list (H6).
When all faults have been acknowledged, the LED "Fault tx
activated" (L11) will be turned off and output for routing
equipment (Fault tx) is "reset" (as in normal operation).
As long as there are faults (not acknowledged faults and/or
acknowledged but not corrected faults) the LED "General fault"
(L7) will be lit and general fault (and maybe general charge fault)
output(s) are activated.
57
Via EBLWin the faults can be set to be not latched. Corrected faults will
in this case automatically disappear from the list without being acknowledged
before.
70
EBL128 Operating Instructions V2.0.x
"More faults"
"Serviced"
= the fault is already
will never be shown if the faults
"Serviced"
is added after the time.
= more than one
57
It

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents