16.2.1.3
16.2.1.4
16.2.1.5
16.2.1.6
Press "" (to see the next fault).
Display disablements (X3)
NOTE! Also zones in "Test mode" will be displayed via this menu.
001 ZONE-ADDR 12-45 LAST ZONE 12
Display disablements
Press "A"
001 ZONE-ADDR 12-45 LAST ZONE 12
Zone XX address XX disabled
Press "" (to see the next disablement).
NOTE!
After all disablements will zones in "Test mode" be
displayed.
001 ZONE-ADDR 12-45 LAST ZONE 12
Zone in TEST MODE: 01
Disable zone (X4)
001 ZONE-ADDR 12-45 LAST ZONE 12
Disable zone
Press "A"
001 ZONE-ADDR 12-45 LAST ZONE 12
Disable zone: 00
Write a zone number (01 – 99) and press "A". If more zones are to be
disabled, repeat the procedure.
Disable zone / address (X5)
This function is useful e.g. for a manual call point not to continue to
generate alarms because of a broken glass.
001 ZONE-ADDR 12-45 LAST ZONE 12
Disable zone-address
Press "A". E.g.:
001 ZONE-ADDR 12-45 LAST ZONE 12
Disable zone: 00 Address: 00
Write a zone-address and press "A". If more zone-addresses are to be
disabled, repeat the procedure.
Re-enable zone (X6)
001 ZONE-ADDR 12-45 LAST ZONE 12
Re-enable zone
Press "A". E.g.:
47
EBL128 Operating Instructions V2.0.x
No. 01
ACCEPT?
No. 01
No. 01
02
03
04
No. 01
ACCEPT?
No. 01
ACCEPT?
No. 01
ACCEPT?
No. 01
ACCEPT?
No. 01
ACCEPT?
X3
X4
X5
X6