Maintenance (H8); Disconnect / Re-Connect Com Loop (H8/S1) - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
31
31.1
Action
"Access"
Scroll to menu H8.
"A"
"A"
or
"Return"
"A"
or
"Return"
"A"
"Return"
Rev: -

Maintenance (H8)

Only authorised personnel have access to the level 3A menus. User
name and Password for level 3A (Service Personnel) are required.
Disconnected
(disabled)
"Disablements" (L8) and is listed in menu H4/U1.

Disconnect / Re-connect COM loop (H8/S1)

To avoid damage on the units and EBL128 during physical connection
/ disconnection of loop units, it is highly recommended to have the
loop disconnected (disabled), i.e. the loop is voltage free (dead).
NOTE! When you disconnect and re-connect the COM loop, all the
statistics shown in menu H5/A6 will be erased and set to "0".
Text in display
Maintenance
Disconnect / Re-connect COM loop
COM-loop is connected.
Press ACCEPT to disconnect
COM-loop is disconnected.
Press ACCEPT to re-connect
Disconnect / Re-connect COM loop
Maintenance
EBL128 Operating Instructions V2.0.x
loop,
etc.
ACCEPT? H8
ACCEPT? S1
ACCEPT? S1
ACCEPT? H8
126
is
indicated
by
LED
Comments
According to chapter
"Access", see page 81.
Depending on if the COM
loop shall be disconnected
or re-connected, press "A"
or "Return"
Scroll or press "Return" to
H8.
Scroll or press "Return".