New Zealand FB Silence switch ("outside switch") is turned ON, i.e.
from not activated to activated state.
FAULT: FBP x
FBP=1826 / 1828 (Ext. Fire Brigade Panel)
The ext. FBP is programmed as another type of unit than the SSD says
or a faulty unit.
FAULT: Fuse on COM-loop
Fuse F4 on the main board is broken. The fuse is not replaceable.
There are more components broken, i.e. the main board has to be
repaired / replaced.
FAULT: High current consumption in CU
EBL128 current consumption, including battery charging, is over 1.8
A, and because of this, the battery charging is turned off. The current
consumption, excluding battery charging, exceeds 0.8 A and the
battery charging is turned off as long as the current consumption
exceeds 0.75 A. (Normally this fault only appears when starting up /
expanding an EBL128.)
FAULT: Input
A fault on the supervised input I0 in EBL128.
Check the cables / connections (cut-off or short-circuit).
FAULT: Input x exp board x
A fault on the supervised input x on the expansion board (4583) with
address x.
Check the cables / connections (cut-off or short-circuit).
FAULT: Interlocking input AA/PP
AA/PP = Area-Point.
An interlocking input is not activated within the time set for fault
activation (5-255 seconds). The time is counted from the activation of
the output (in the interlocking combination, area / point).
62
EBL128 Operating Instructions V2.0.x