FAULT: Short-circuit SCI nn <-> SCI nn
SCI nn <-> SCI nn describes between which Short Circuit
Isolators (SCI:s) the short-circuit is located.
nn = A, B, 0, 1, 2, 3, 4, 5, 6 or up to 63. A & B is the built-in isolator
in the EBL128 A-direction and B-direction respectively, i.e. if no SCI
is used the information will always be: SCI A <-> SCI B.
If one SCI (no. 0) is used, the information will be:
SCI A <-> SCI 0 or SCI 0 <-> SCI B
...and so on.
There will also be a "FAULT: No reply ....." message for each unit
that EBL128 cannot find.
If there are several short-circuits on the loop the message shows the
last isolator before the break in the A-direction (incl. the following
isolator). There will also be shown "FAULT: Several faults ...".
th
NOTE! Each 10
minute a new attempt is made to communicate in
the A-direction only.
When all short-circuits are repaired (corrected) the communication
automatically returns to communicate in the A-direction only.
FAULT: Site specific data (SSD)
The Site Specific Data (SSD) is not downloaded correctly (a
checksum fault, etc.).
required. If the fault cannot be corrected it is very serious. Call for
service personnel / engineer immediately.
FAULT: Site specific data (SSD), AAU x
AAU=1735 / 1736 (Alert Annunciation Unit)
There is no SSD (Site Specific Data) downloaded to the unit or
something is wrong in the downloaded SSD.
FAULT: Site specific data (SSD), EPU x
EPU=1728 (Ext. Presentation Unit)
There is no SSD (Site Specific Data) downloaded to the unit or
something is wrong in the downloaded SSD.
56
The fault has to be acknowledged and it can last up to 10 minutes before
the communication returns to communicate in the A-direction only.
68
EBL128 Operating Instructions V2.0.x
A new SSD download (via EBLWin) is
56