Re-Enable Zone / Address (H2/B6) - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
25.6
Action
"Access"
Scroll to menu H2:
"A"
Scroll to menu B6.
"A"
"A" (to re-enable)
or
"Return"
"Return"
Rev: -

Re-enable zone / address (H2/B6)

Disabled alarm points (zone – address) are listed in menu H4/U1.
Re-enabling via this menu has higher priority than automatic re-
enabling.
Alarm points / Zones disabled via the "Encapsulation function", see
chapter "Single with automatic disablement" page 54, have to be re-
enabled via this menu before they can activate a new alarm.
A zone will be presented as ZZ - 00 (ZZ=01-99).
Alarm points (zone – address) disabled when the "New Zealand FB
Silence switch" (outside switch) is turned OFF, have to be re-enabled
via menu B5 or B6 before they can activate a new alarm.
When all alarm points have been re-enabled, the LED "Disablements"
(L8) will be turned OFF, if there are no other disablements.
If there is nothing to re-enable, --- List is empty --- will be
shown.
Text in display
Disable or re-enable
Disable zone
Re-enable zone-address
Re-enable zone: 01 Address: 01
Re-enable zone-address
Disable or re-enable
EBL128 Operating Instructions V2.0.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B6
ACCEPT?
ACCEPT? B6
ACCEPT? H2
92
Comments
According to chapter
"Access", see page 81.
L=A list in which you can
L
scroll.
Press "A" to accept. You
will stay in this list until all
zone-addresses are re-
enabled or press "Return"
to menu B6.
If more re-enabling shall
be done, continue like
above. If not, scroll or
press "Return" to menu
H2.
Scroll or press "Return".