Perform Zone Test (Test Mode) (H7) - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
30
Action
"Access"
Scroll to menu H7.
"A"
"A"
E.g. "01"
"A"
"A"
"Return"
The zone(s) will stay in test mode until the test mode is ended. The test mode will also be automatically
ended 60 minutes after the last testing in the zone.
Perform the test as quickly as possible, since the output(s) for routing equipment (fire brigade tx) are disabled
(also the parts of the zones in test mode, not visible for the test personnel, are disabled).
Rev: -
Perform ZONE TEST (test mode)
(H7)
Normally, zones are tested during the monthly test via menu H1, see
page 83. Via menu H7 it is possible to solely perform the zone test.
Up to 99 zones can be in test mode at the same time.
In test mode, only the alarm points are tested, i.e. no outputs (no
sounders) will be activated during the test. (Alarm devices can be
tested via menu H8/S6.) See also NOTE! b) below.
If a real fire alarm is activated by an alarm point not in test mode,
the normal fire alarm functions will be activated, i.e. fire alarm
presentation, outputs (sounders) activated, routing equipment (fire
brigade tx) activated, etc. but the zone(s) in test mode will remain in
test mode until the test mode is ended. During the fire alarm the
zone(s) in test mode can be displayed via menu X3, see chapter
"Display disablements (X3)", page 47.
See also chapter "The display in EBL128", page 21.
There will be an automatic ending of the test mode one hour after the
latest tested alarm point / zone.
NOTE! If the door in EBL128 is left open, the output(s) for routing
equipment (fire brigade tx) might be disabled (if set so in EBLWin).
Text in display
Perform ZONE TEST
Set zone in test mode
Set zone: 00 in test mode
Zone 01 in test mode
Set zone: 00 in test mode
Set zone in test mode
EBL128 Operating Instructions V2.0.x
ACCEPT? H7
ACCEPT? D1
Start test:
ACCEPT
Start test:
ACCEPT
ACCEPT? D1
124
Comments
According to chapter
"Access", see page 81.
D1 = Sub menu to set a
zone in test mode.
Write the zone number and
press "A".
LED "Test mode" (L9)
will light up.
If more zones shall be set
in test mode, do like
above, else press "Return".