Fire Alarm - Panasonic EBL128 Operating Instructions Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01623
Rev: -
16.2
 On the second row, an alarm text (= the fire alarm text) will
be shown (if programmed).
Example; pre-warning zone 12, address 45 (within zone 12):
Pre-warning detector 12-45
(alarm text)
Example; pre-warning zone 12:
Pre-warning zone 12
(alarm text)
LEDs "Alarms queued" (L2) blinking are indicating more than
one pre-warning and they will be automatically scrolled (each
th
5
second).
Pre-warning is automatically reset see chapter "Alarm reset", page 53.

Fire alarm

256 alarms (points or zones) can be presented in the EBL128 display.
See also chapter "The display in EBL128", page 21. According to the
EN54-2 standard, in case of a fire alarm, the following will happen:
 The buzzer in EBL128 sounds 0.4 sec. each 0.8
0.4 sec.).
 LEDs "Fire" (L1) are blinking (0.4 / 0.4 sec.).
 Output for routing equipment (Fire brigade tx) is activated.
See also NOTE! below.
 Programmable outputs for fire alarm are activated.
 In the EBL128 display (and ext. FBP display), the fire
alarm(s) will be presented. See below.
NOTE! Normally the c.i.e. relay output "R0" is used as the output for
Routing equipment (Fire brigade tx).
activated for fire alarm from any alarm point or zone line input.
If the fire alarm routing equipment has provision for transmission of
several fire alarm signals and the alarm receiver has provision for
reception of several fire alarm signals, the alarm receiver can take
different actions depending on if it is a fire alarm type A or B.
If a fire alarm type B is received, it will indicate that only one analog
addressable smoke, heat or multi detector is activated, which could be
a nuisance alarm.
If a fire alarm type A is received, it is probably a real fire since fire
alarm is then activated from:
 Two or more analog addressable smoke, heat or multi
detectors.
37
Programmable outputs for "General fire alarm" and for the activated fire
alarm(s).
42
EBL128 Operating Instructions V2.0.x
th
sec. (0.4 /
The output will then be
37