Power Cabinet Ac Current Requirements - Motorola SC 4812ET RF Hardware Installation Manual

Power cabinet
Table of Contents

Advertisement

Cabinet Cabling
– continued
Figure 5-11: International and North American AC Load Center Wiring
N
G
5
NOTE:
L = Line
N = Neutral
G = Ground
Power Cabinet AC Current
Requirements
Number of Sector–Carriers
116
International AC Load Center
Table 5-32 lists the number of sector–carrier AC current ratings for the
Power Cabinet.
Table 5-32: Power Cabinet AC Current Requirements
1
3
6
9
SC
4812ET RF and Power Cabinet Hardware Installation Manual
TM
WARNING
Ground MUST be connected first. Electric shock hazard
exists if any other sequence is used.
G
N
L
North American AC Load Center
AC to Pilot Beacon
FW00475
Number of Rectifiers
3
4
5
DRAFT
NOTE:
L 1= Line 1
L 2= Line 2
N = Neutral
G = Ground
Power Cabinet AC Current
2
Ratings
60A (90A Non–Continuous)
71A (101A Non–Continuous)
86A (116A Non–Continuous)
Apr 2001
L1
L2
V04.03

Advertisement

Table of Contents
loading

Table of Contents