Motorola SC 4812ET RF Hardware Installation Manual page 147

Power cabinet
Table of Contents

Advertisement

Number of Rectifier
Modules
4
4
5
SC 614 DC Power
Connection
Apr 2001
SC
TM
V0D.03
SC 4812ET/SC 614 BTS DC Power Sharing
The SC 614 MUST NOT be connected to an AC source in
this configuration. As shown in Figure D-1, AC should
ONLY be connected to the SC 4812ET Power Cabinet. To
ensure that accidental AC connection cannot occur to the
SC 614, the four AC Power cables that connect from the
SC 614 AC Load Center to each of the Power Supply units
should be removed. Failure to do this could result in
damage to the SC 614 Power Supplies and misoperation of
the entire system.
Due to the reduction in load capacity of the power cabinet, the
battery/rectifer configuration and number of sector–carriers that can be
supported in the SC 4812ET RF Cabinet are changed compared to the
standard SC 4812ET documentation.
Table D-1: Battery/Rectifier Configuration
Number of Battery
Strings
8
12
10
The objective of this procedure is to connect the DC power cable from
the Power Cabinet to the SC 614 BTS.
Battery Power must be removed from the system until all
connections are made to the BTS.
4812ET RF and Power Cabinet Hardware Installation Manual
CAUTION
SC 4812ET Sector
Carriers
3
3
6
WARNING
DRAFT
– continued
System Battery Backup
Time (hours)
4
6
4
147