7.2
Outside air temperature via Konnex
bus (CLC02, RAD01)
The outside air temperature must be provided as bus information to all applications with
radiators. It can be read via the following S-mode communication object:
Outside temperature (input communication object)
Flags
Type
R W C T U
0 1 1 1 1 9.001
DPT_Value_Temp
Subject to the appropriate configuration and integration, the outside air temperature is
read by the controller immediately after a reset.
In LTE mode, the outside temperature is sent in a zone intended specifically for that
purpose.
Outside temperature input (input)
Possible partner function blocks)
TempOutside
320 OTS
Room Temperature Sensor
Outside temperature
zone
RXB (KNX) Applications library
Temperature measurement
Receive timeout
Yes
CLC and RAD description of functions for CC-02 CM110384en_03
Value
Floating point (°C)
Known partner devices
Siemens:
Synco RMH760
RMU710 / 20 / 30
RMB795 / RMS705
28 Feb 2009