Connection diagrams
Connection of
field devices, room
unit, KNX / EIB bus
and power supply
Note
Siemens
Building Technologies
N1
B1
1
T
M
2
4
D1
GND
5
D2
6
Y1
7
G
8
Y2
9
Y3
10
11
G
Y4
12
2
CP –
13
PPS2
1
14
CP +
4
CE +
15
KNX / EIB
CE –
16
3
CE +
17
KNX / EIB
CE –
18
N
19
N
N
19
AC 230 V
L
21
L
L
21
N.C.
22
Q43
23
Q44
24
Q13
25
26
1
Q14
2
27
Q24
3
Q34
28
N1
RXB21.1, RXB22.1
B1
LG-Ni 1000 temperature sensor
D1, D2
Volt-free contacts (window contact, occupancy sensor, etc.)
Y1...Y4
AC 24 V thermic valve actuators
Y1.1
Motorized AC 24 V, 3-position valve or damper actuator
Y3.1
Motorized AC 24 V, 3-position valve or damper actuator
B2
QAX... room unit
Q1
3-speed fan
Q1.1
1-speed fan
Q2
Electric heating coil
Twisted pair
Fans connected to relay outputs Q14 ... Q34 must not be operated in
parallel. For parallel operation use cut-off relays or slave room controllers.
At Q2 (1.8 kW max. resistive load), use additional external fuses of max. 10 A
to protect the pcb tracks.
For information on the compatibility of field devices with the RXB21.1 and RXB22.1
room controller, refer to the various application descriptions (see the FNC description of
functions, document CA110385)
RXB21.1, RXB22.1 Room controllers
B1
D1
D2
Y1
Y1.1
GL
M
Y2
Y3
M
Y3.1
GL
Y4
B2
L
Q2
N
L
1
N
Q1
L
N
Q1.1
CM2N3873en_06
13/16
02 Apr 2010

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Desigo rxc, desigo rxb, desigo rxl, desigo rxa

Table of Contents