Parameter: Local comfort mode
K N X
CO
R
Siemens
Building Technologies
The following LTE-mode communication object is provided for central control:
Enable Comfort (input)
Possible partner-function blocks
EnableComfort
110 HVACS
HVAC-Mode Scheduler
Timeswitch zone
104 PMC
Programme to HVAC-Mode Conversion
The states are:
State
Enabled
Disabled
Comfort and Precomfort are enabled locally in the controller with the following
parameter in the Room unit menu, page 138:
Description
Switch from Economy to Precomfort or Comfort mode
Enabled (basic setting)
Means that Precomfort or Comfort can be disabled via the
Enable Comfort input.
Disabled (ignore Enable Comfort input) In this case
Precomfort or Comfort CANNOT be disabled via the
Enable Comfort input
5.5.3
Central control of room operating mode via
Room operating mode input
Local
Central (ACS)
Controller
Prio
Central
(Synco controller)
DI
DI
PPS2
Room operating mode (input)
Possible partner-function blocks
110 HVACS
HVACMode
HVAC-Mode Scheduler
Timeswitch zone
104 PMC
Programme to HVAC-Mode Conversion
RXB (KNX) application library
Room operating modes
Description
Priority 3 influences ( RoomOperatingMode, presence
detector, room unit) are enabled
Priority 3 influences are disabled.
The effective room operating mode is Economy.
The following LTE-mode communication object is used
to control the room operating mode from a building
0.
automation and control system:
1.
1.
2.
3.
3.
3.
FNC Description of functions for FC-10, FC-11, FC-12
Known partner devices
Siemens:
Synco
RMB795
HandyTool
*105
1
0
Known partner devices
Siemens:
Synco RMU710 / 20 / 30
RMH760 / RMB795
59/166