Siemens Desigo RXB Technical Manual page 47

Technical manual
Table of Contents

Advertisement

Disposal
Engineering notes
AC 230 V
supply cables
Volt-free
relay outputs
AC 230 V
AC 24 V triac outputs
Example:
Siemens
Building Technologies
The device is classified as waste electronic equipment in terms of the European
Directive 2002/96/EC (WEEE) and should not be disposed of as unsorted municipal
waste.
The relevant national legal rules are to be adhered to.
Regarding disposal, use the systems setup for collecting electronic waste.
Observe all local and applicable laws.
The KNX / EIB Building Services Management Manual and system principles supple-
ment (see "Reference documentation", page 10) contains the information relevant for
the engineering of the KNX / EIB bus (topology, bus repeaters, etc.) and for the
selection and dimensions of connecting cables for the supply voltage and field devices.
 The RXB2... room controllers operate with a mains supply voltage of AC 230 V. The
controlled devices (valves and damper actuators) receive their power directly from
the room controller. This means that a separate AC 24 V supply is not necessary for
the controllers and associated field devices.
 The sizing and fuse protection of the power supply cables depends on the total load
and on local regulations. The power supply cables connected to the room controller
must be secured with cable restraints.
 If serial wiring is applied on the terminal block 19/21, the connection will be inter-
rupted if the block is removed from the controller (the jumpers 19-19 and 21-21 are
on the PCB, not in the block, see terminal diagrams on pages 11 and 12)
 The supply cables must be secured with cable restraints.
 The volt-free relay outputs allow the switching of loads up to AC 250 V, 5 A (4 A).
The heating coil relay in the RXB22.1 switches resistive loads up to 1.8 kW.
The cable dimensions depend on the connected load and the local installation
regulations.
 The circuits must be externally fused ( 10 A) as there are no internal fuses.
 The cables connected to the room controller must be secured with cable restraints.
The fans must not be connected in parallel.
The simultaneous load on outputs Y1 ... Y4 must not exceed 9.5 VA.
Y1 (heating)
2 thermic valve actuators, type STP72E
Y2 (cooling)
2 thermic valve actuators, type STP72E
Y3, Y4 (outside air)
3-position damper actuator 4.5 VA
The maximum load is 9.5 VA for the heating sequence and 9.5 VA for the cooling
sequence.
This is acceptable because the two sequences never operate at the same time.
With low loads (< 2VA) the voltage tolerance may be greater than +20%
(see technical data).
RXB21.1, RXB22.1 Room controllers
5 W
5 W
4.5 VA
7/16
CM2N3873en_06
02 Apr 2010

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Desigo rxc, desigo rxb, desigo rxl, desigo rxa

Table of Contents