13.5.2 S-Mode Output Communication Objects - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Name
Alarm info
Analog input B1
Common alarm.
Cooling coil output
Digital input 1
Digital input 2
Effective application mode
Effective occupancy
Effective room operating mode
Effective room operating mode
Comfort
Effective room operating mode
Economy
Effective room operating mode
Precomfort
Effective room operating mode
Protection
Effective room temperature
Effective setpoint
Effective setpoint cooling
Effective setpoint heating
Effective setpoint offset
Electrical power
Energy demand room
Fan output
Heating coil output
Heating/cooling output
Heating outp bus el heating
Heating surface output
Master/slave HVAC controller
output
Master/Slave room unit output
Outside air damper.
Presence detector output
Present setpoint.
Present setpoint ...
(6 indiv. values)
Present setpoints cooling
Present setpoints heating
Return air temperature output
Room temperature output
Status
Supply air temperature output
Window switch output
Siemens
Building Technologies

13.5.2 S-mode output communication objects

Flags:
R
Read
W Write
C
Communication
Flags:
R W C T U
1
0 1 1 0 219.001
1
0 1 1 0 9.001
1
0 1 1 0 1.005
1
0 1 1 0 5.001
1
0 1 1 0 1.001
1
0 1 1 0 1.001
1
0 1 1 0 20.105
1
0 1 1 0 20.003
1
0 1 1 0 20.102
1
0 1 1 0 1.001
1
0 1 1 0 1.001
1
0 1 1 0 1.001
1
0 1 1 0 1.001
1
0 1 1 0 9.001
1
0 1 1 0 9.001
1
0 1 1 0 9.001
1
0 1 1 0 9.001
1
0 1 1 0 9.002
1
0 1 1 0 9.024
1
0 1 1 0 6.001
1
0 1 1 0 5.001
1
0 1 1 0 5.001
1
0 1 1 0 1.100
1
0 1 1 0 5.001
1
0 1 1 0 5.001
1
0 1 1 0 C.S.
1
0 1 1 0 C.S.
1
0 1 1 0 5.001
1
0 1 1 0 1.018
1
0 1 1 0 9.001
1
0 1 1 0 9.001
1
0 1 1 0 222.100
1
0 1 1 0 222.100
1
0 1 1 0 9.001
1
0 1 1 0 9.001
1
0 1 1 0 C.S.
1
0 1 1 0 9.001
1
0 1 1 0 1.019
RXB (KNX) application library
KNX information
T
Transmit
U
Update
1)
C.S. = Company specific
For internal use only
Data point type (KONNEX)
DPT_AlarmInfo
DPT_Value_Temp
DPT_Alarm
DPT_Scaling
DPT_Switch
DPT_Switch
DPT_HVACContrMode
DPT_OccMode
DPT_HVACMode
DPT_Switch
DPT_Switch
DPT_Switch
DPT_Switch
DPT_Value_Temp
DPT_Value_Temp
DPT_Value_Temp
DPT_Value_Temp
DPT_Value_Tempd
DPT_Power
DPT_Percent_V8
DPT_Scaling
DPT_Scaling
DPT_Heat/Cool
DPT_Scaling
DPT_Scaling
1)
13 Byte
1)
4 Byte
DPT_Scaling
DPT_Occupancy
DPT_Value_Temp
DPT_Value_Temp
DPT_TempRoomSetpSetF16[3]
DPT_TempRoomSetpSetF16[3]
DPT_Value_Temp
DPT_Value_Temp
1)
2 Byte
DPT_Value_Temp
DPT_Window_Door
FNC Description of functions for FC-10, FC-11, FC-12
Send
See
heartbeat
page
134
yes
138
yes
yes
134
89, 93
yes
137
no
137
no
128
yes
41, 51
yes
43, 54
yes
43, 54
yes
43, 54
yes
43, 54
yes
43, 54
yes
78
yes
70
yes
70
yes
70
yes
75
yes
100
yes
127
yes
113
yes
89, 93
yes
84
yes
97
yes
102
yes
118
yes
118
yes
107
yes
40
yes
yes
70
yes
70
yes
70
yes
78
yes
78
yes
no
142
110
yes
37, 49
yes
145/166
CM110385en_05
28 Feb 2009