Local Control Of Room Operating Mode Via The Window Contact Input - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Effective room operating
mode
Window contact
K N X
CO
R
48/166
Siemens
Building Technologies
5.4.1
Local control of room operating mode via the
window contact input
Central
Local
Controller
Prio
S
1.
S
DI
1.
3.
S
S
S
3.
DI
3.
PPS2
3.
S
The table below shows the effective room operating mode as a function of the Window
contact input.
Status of window
contact
Window closed
Window open
The window contact is connected directly to a digital input on the room controller (see
page 126). Alternatively an EIB/KNX window contact (connected to the bus) may be
used. The application evaluates both items of information (logic OR operation).
Since EIB/KNX window contacts are available from a variety of manufacturers, the
name of the S-mode output communication object varies accordingly.
Window contact on DI
EIB / KNX window contact
The following S-mode communication object is used to integrate an EIB/KNX window
contact:
Window contact input (Input communication object)
Flags
Type
R W C T U
0 1 1 0 0 1.019
DPT_WindowDoor
RXB (KNX) application library
Room operating modes
Whenever a window is opened, the room controller
always switches to the Protection room operating mode,
i.e. the heating or cooling output is reduced to a
minimum.
Effective room operating mode
No effect.
Operating mode is determined by inputs with a lower priority
Protection mode
Room controller RXB...
Window contact input
Receive timeout
No
FNC Description of functions for FC-10, FC-11, FC-12
OR
Window contact output
10385Z10en
States
0 = Closed
1 = Open
CM110385en_05