Window Switch (Lte Mode); Presence Detector (Lte Mode) - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Notes
HandyTool
Siemens
Building Technologies
• The master/slave function requires that all 3 M/S zones have the same name
• If the master/slave function is not required, the M/S zone should be disabled (to limit
the load on the bus).
Parameter
Short name
*021
Master/Slave
*022
Master/Slave zone (apart.)
*023
Master/Slave zone (room)
*024
Master/Slave zone (subzone)
Parameter
*021 Master/Slave

10.2.1 Window switch (LTE mode)

For master/slave mode, only the master's window switch is evaluated without special
measures, which also influences the slave controllers.
Window switches on the slaves are NOT considered.

10.2.2 Presence detector (LTE mode)

For master/slave mode, only the master's presence detector is evaluated without
special measures, which also influences the slave controllers.
Presence detectors on the slaves are NOT considered.
RXB (KNX) application library
Master/slave
Setting
Master
Slave
FNC Description of functions for FC-10, FC-11, FC-12
Basic setting
Master
1
–1 (out of service)
1
HandyTool
1
0
CM110385en_05
28 Feb 2009
121/166