5.4
Determine the room operating mode with
third-party products (S-mode)
In S-mode the effective room operating mode of the room controller depends on the
central Room operating mode time schedule and/or on local influences such as window
contacts, presence detectors or room units.
The diagram below shows how these influences are processed by the room controller,
and their priority:
Central
Local
Window contact
Room operating mode
S
Presence detector
Room unit
Temporary
Comfort mode
• The effects of Priority 1 and Priority 2 are similar in nature to continuous states
• The Priority 3 influences are treated as events .
The key factor is the moment at which the state changes (trigger edge).
If the mode is later changed by another source of priority 3, the last change
applies.
RXB (KNX) application library
Room operating modes
Controller
Prio
S
1.
DI
1.
3.
S
3.
DI
3.
PPS2
3.
S
FNC Description of functions for FC-10, FC-11, FC-12
S
Effective
room op. mode
S
Effective
occupancy
47/166
CM110385en_05
28 Feb 2009