11.17.3 Mapping the sensor B1 to the Konnex bus

RXB... Room controller
B1
Temperature sensor B1 can also be connected to the bus in S-mode as a universal
temperature (e.g. outside temperature). To do this, the temperature sensor must be
parameterized as "only meas value acquisition" (see page 76.)
Analog input B1 (Output communication object)
Flags
Type
R W C T U
9.001
1 0 1 1 0
DPT_Value_Temp

11.18 Software version

The present software version can be read via the HandyTool
(not available for devices with index A).
Parameter
Application set
Application version
Operating system version
KNX interface version
*) This information serves to identify the controller's software version. You can use it in
case of a service request.
11.19

Device state

If the application is ready (loaded and tested), parameter 240 is set to 1.
Parameter
Device state
In Service mode the device state is always = 0 because the application is not running.
RXB (KNX) application library
General and central functions
Analog input B1
Send heartbeat
Yes
HandyTool
*236
424 = RXB21.1/FC-10
425 = RXB21.1/FC-11
426 = RXB22.1/FC-12
427 = RXL21.1/FC-10
428 = RXL21.1/FC-11
429 = RXL22.1/FC-12
*237 *)
*238 *)
*239 *)
HandyTool
*240
FNC Description of functions for FC-10, FC-11, FC-12
10385Z201en
States
CM110385en_05
28 Feb 2009