Filter Worksheets - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Siemens IP router
Note
Siemens
Building Technologies
We recommend the Siemens IP router, ordering:
5WG1 146-1AB01, short description N146
Bus connection via bus terminals, IP network connection via RJ45 plug
Additional information is available in the product and function description (including
with each device) or at:
For large plants with Synco, use Siemens IP routers as of version R4 (stamped
R4), since only these IP routers contain the LTE filter worksheet (see Section
4.5.8.2).
4.5.8

Filter worksheets

4.5.8.1
S-mode filter worksheet
The filter worksheet for plants, working in S-mode, are automatically calculated by
the ETS (EIB Tool software) and can then be loaded to the coupler.
4.5.8.2
LTE mode filter worksheets (predefined)
It responds differently in the LTE mode. Filter worksheets for the zone are
predefined in the couplers. The zones must be assigned accordingly during
engineering.
Relevant zone are predefined for RXB / RXL
Zones
Geographical zone (apartment)
Timer zone (apartment)
Master/Slave zones (apartment)
Heat distribution zones
Refrigeration distribution zones
Outside temperature zone
For more information on Synco and LTE mode, see CE1P3127
Installation guide RXB, RXL
Konnex bus technology
www.automation.siemens.com/et/gamma/
LTE telegrams with the following
zone addresses are...
locked
forwarded
1 ... 110
111 ... 126
1 ... 110
111 ... 126
1 ... 110
111 ... 126
1 ... 15
16 ... 31
1 ... 15
16 ... 31
1 ... 15
16 ... 31
CM110381en_01
21 / 22
28 Feb 2009