Parameter

Temporary Comfort mode

Parameter
On-delay occupancy sensor
Off-delay occupancy sensor
ETS3 Professional
ACS Service
HandyTool
Parameter
Heat demand signal
Cooling demand
signal
Siemens
Building Technologies
10.3
Temporary Comfort mode
If the room controller is set to Economy and the associated room unit is switched to
Auto (Comfort), the room controller maintains Comfort for the period defined by the
temporary comfort mode time and then returns to Economy. This function is only
available if the room unit concerned has an
10.4
Presence detector switch-on and switch-off
delay
A switch-on or switch-off delay can be applied to the presence detector function. The
room controller only switches to Comfort ( or to Precomfort or Economy) after the delay
time is expired.
10.5

Heating and cooling demand

To provide the required heating or cooling energy, the heating and/or cooling demand
from each room is transmitted to the building automation and control system.
For a more in-depth understanding of heating and cooling demand, see the application
example in section 3.4 .
The function can be disabled in the room controller with ETS.
The parameter is not available.
See the parameter in the last column of the following table.
Description
Heating demand transmitted to the BAC system.
Cooling demand transmitted to the BAC system.
Parameter
Range
*131, *132
0 = Disabled/ Off
1 = Enabled / On
RXB (KNX) Applications library
General / central functions
Auto button (see also pages 40 and 51).
Basic
setting
Range
60 min
0 ... 360 min
Basic
setting
Range
5 min
0 ... 90 min
5 min
0 ... 90 min
Basic setting
CLC and RAD description of functions for CC-02 CM110384en_03
Resolution
HandyTool
1 min
*117
Resolution
HandyTool
1 min
*119
1 min
*120
HandyTool
*131
*132
0 = Disabled