Siemens Desigo RXB Technical Manual page 449

Technical manual
Table of Contents

Advertisement

Configuration
Menu
Communication
Room temperature setpoints
Other setpoints
Sequences
Motorized and electromechanic Runtime
Motorized Offset
LTE mode Heating coil outp bus valve
Fan control.
Room unit
With LCD Display heating/cooling symbols
Siemens
Building Technologies
The following parameters are available with application FNC12.
They are set via ETS, ACS, or HandyTool.
Parameters.
Communication mode
Receive timeout
Send heartbeat
Protection cooling setpoint
Economy cooling setpoint
Precomfort cooling setpoint
Comfort cooling setpoint
Comfort heating setpoint
Precomfort heating setpoint
Economy heating setpoint
Protection heating setpoint
Downdraft compensation
Outside temp 0% valve pos
Outside temp max valve pos
Maximum valve pos
Control sequence
Actuator type heating/cooling coil valve
Actuator type heating surface valve
Cooling coil outp bus valve
Heating surface outp bus valve
Fan speeds
Fan control.
Minimum on time.
Temperature sensor B1
Periodic fan kick Comfort
Periodic fan kick Economy
Measured value correction
Setpoint offset range
Local Comfort mode
Room unit
Temperature unit
Standard display
Setpoint display
RXB application library (KNX)
FNC18 – Two-pipe fan coil (changeover) and radiator
Values/Range
S-mode / LTE and S-mode
0 ... 105 min.
0 ... 105 min.
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
–30 ... 10°C
–30 ... 10°C
0 ... 100%
– Heating only
– Cooling only
– Changeover
– STA71
– STA72E
– STE71
– STE72
– STP71
– STP72E
– Motorized 3rd devices
rd
– Thermal 3
devices
– Motorized bus
– STA71
– STA72E
– STE71
– STP71
– STP72E
– Motorized 3rd devices
rd
– Thermal 3
devices
– Motorized bus
0 ... 360 s
0 ... 360 s
Off/On
Off/On
Off/On
– External control
– 1-speed/2-speed/3-speed
Manual / Auto
1 ... 10 min
– Room
– Return air
– Measured value only
– No sensor
0 ... 90 min (90min = Off)
0 ... 360 min (360min = Off)
– 3 ... 3 K
± 0 ... 10 K
Enabled / Disabled
Without LCD / with LCD
Enabled / Disabled
°C or °F
No display / Room
temperature / Setpoint
Absolute / Relative
FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12
Basic setting
S-mode.
60 min.
45 min.
40 °C
35 °C
28 °C
24 °C
21 °C
19 °C
15 °C
12 °C
0°C
–10°C
100%
Cooling only
STP72E
– SSA81
– SSB81
– SSP81
– SQS81
– SSA81
STA72E
– SSB81
– SSP81
– SQS81
150 s
0 s
Off
Off
Off
3-speed
Auto
6 min
No sensor
90 min (Off)
360 min (Off)
0 K
± 3 K
Enabled
Without LCD
Enabled
°C
Room temperature.
Relative
CM110672en_03
30.11.2007
47/52