(4.35 - Siemens SITRANS P Brochure & Specs

Measuring instruments for pressure
Table of Contents

Advertisement

Transmitters for gage, absolute and differential pressure, flow and level
Technical specifications
SITRANS P, DS III series, for differential pressure and flow
Input
Measured variable
Spans (infinitely adjustable) or
nominal measuring range and
max. permissible working pressure
Lower measuring limit
• Measuring cell with silicone oil filling
Upper measuring limit
Output
Output signal
• Lower limit (infinitely adjustable)
• Upper limit (infinitely adjustable)
Load
• Without HART communication
• With HART communication
Physical bus
With polarity reversal protection
Accuracy
Reference conditions
(All error data refer always refer to the set
span)
Error in measurement and fixed-point setting
(including hysteresis and repeatability)
• Linear characteristic
- r
10
- 10 < r
30
- 30 < r
100
• Square-root characteristic (flow > 50%)
- r
10
- 10 < r
30
© Siemens AG 2008
SITRANS P measuring instruments for pressure
HART
Differential pressure and flow
Span
Maximum working pres-
sure
1 ... 20 mbar
32 bar
(0.4015 ... 8.031 inH
O)
(464 psi)
2
1 ... 60 mbar
160 bar
(0.4015 ... 24.09 inH
O)
(2320 psi)
2
2.5 ... 250 mbar
(1.004 ... 100.4 inH
O)
2
6 ... 600 mbar
(2.409 ... 240.9 inH
O)
2
16 ... 1600 mbar
(6.424 ... 642.4 inH
O)
2
50 ... 5000 mbar
(20.08 ... 2008 inH
O)
2
0.3 ... 30 bar
(4.35 ... 435 psi)
2.5 ... 250 mbar
420 bar
(1.004 ... 100.4 inH
O)
(6091 psi)
2
6 ... 600 mbar
(2.409 ... 240.9 inH
O)
2
16 ... 1600 mbar
(6.424 ... 642.4 inH
O)
2
50 ... 5000 mbar
(20.08 ... 2008 inH
O)
2
0.3 ... 30 bar
(4.35 ... 435 psi)
-100% of max. span (-33% with 30 bar (435 psi) measuring cell or 30 mbar a (0.44 psi))
100% of max. span (for oxygen version and inert filling liquid; max. 160 bar g (2320 psi g))
4 ... 20 mA
3.55 mA, factory preset to 3.84 mA
23 mA, factory preset to 20.5 mA or optionally set
to 22.0 mA
R
(U
- 10.5 V)/0.023 A in ,
B
H
U
: Power supply in V
H
R
= 230 ... 500
(SIMATIC PDM) or
B
R
= 230 ... 1100
(HART Communicator)
B
-
-
To EN 60770-1
Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling,
room temperature 25 °C (77 °F)) r: Span ratio (r = max. span / set span)
(0.0029 r + 0.071)%
(0.0045 r + 0.071)%
(0.005 r + 0.05)%
0,1%
0,2%
DS III series
for differential pressure and flow
PROFIBUS PA or FOUNDATION Fieldbus
Nominal measuring
Maximum working pres-
range
sure
20 mbar g
32 bar
(8.031 inH
O)
(464 psi)
2
60 mbar
160 bar
(24.09 inH
O)
(2320 psi)
2
250 mbar
(100.4 inH
O)
2
600 mbar
(240.9 inH
O)
2
1600 mbar
(642.4 inH
O)
2
5 bar
(2008 inH
O)
2
30 bar
(435 psi)
250 mbar
420 bar
(100.4 inH
O)
(6091 psi)
2
600 mbar
(240.9 inH
O)
2
1600 mbar
(642.4 inH
O)
2
5 bar
(2008 inH
O)
2
30 bar
(435 psi)
Digital PROFIBUS PA or FOUNDATION Fieldbus
signal
-
-
-
-
IEC 61158-2
Yes
0,075%
0,1%
Siemens FI 01 · 2009
2
2/107