HART communication between a PC communicator and a pressure
transmitter
When parameterizing with a PC, the connection is made through
a HART modem.
The signals needed for communication in conformity with the
HART 5.x or 6.x protocols are superimposed on the output cur-
rent using the Frequency Shift Keying (FSK) method.
Adjustable parameter DS III HART and P300 HART
Parameters
Start of scale
Full-scale value
Electrical damping
Start-of-scale value without application
of a pressure ("Blind setting")
Full-scale value without application of a
pressure ("Blind setting")
Zero adjustment
Current transmitter
Fault current
Disabling of keys, write protection
Type of dimension and actual dimension x
Characteristic (linear)
Input of characteristic
Freely-programmable LCD
Diagnostics functions
1)
Cancel apart from write protection
Diagnostic functions for DS III HART and P300 HART
• Zero correction display
• Event counter
• Limit transmitter
• Saturation alarm
• Slave pointer
• Simulation functions
• Maintenance timer
Available physical units of display for DS III HART and P300
HART
Physical variable
Pressure (setting can also be
made in the factory)
Level (height data)
Volume
Mass
Temperature
Miscellaneous
© Siemens AG 2008
SITRANS P measuring instruments for pressure
Transmitters for gage pressure for the paper industry
Input keys
HART com-
munication
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
1)
x
x
x
x
x
x
x
x
Physical dimensions
Pa, MPa, kPa, bar, mbar, torr, atm,
2
2
psi, g/cm
, kg/cm
, inH
O, inH
O
2
2
(4 °C), mmH
O, ftH
O (20 °C),
2
2
inHg, mmHg
m, cm, mm, ft, in
3
3
3
3
3
m
, dm
, hl, yd
, ft
, in
, US gallon,
lmp, gallon, bushel, barrel, barrel
liquid
g, kg, t, lb, Ston, Lton, oz
K, °C, °F, °R
%, mA
SITRANS P300 and DS III series
with PMC connection – Technical description
Parameterization through PROFIBUS PA interface
Fully digital communication through PROFIBUS PA, profile 3.0, is
particularly user-friendly. The PROFIBUS puts the DS III PA is in
connection with a process control system, e.g. SIMATIC PSC 7.
Communication is possible even in a potentially explosive envi-
ronment.
For parameterization through PROFIBUS you need suitable soft-
ware, e.g. SIMATIC PDM (Process Device Manager).
Parameterization through FOUNDATION Fieldbus Interface
Fully digital communication through FOUNDATION Fieldbus is
particularly user-friendly. Through the FOUNDATION Fieldbus
the DS III FF is connected to a process control system. Commu-
nication is possible even in a potentially explosive environment.
For parameterization through the FOUNDATION Fieldbus you
need suitable software, e.g. National Instruments Configurator.
Adjustable parameters for DS III PA and FF and P300 PA and FF
Adjustable parameters
Electrical damping
Zero adjustment (correction of
position)
Key and/or function disabling
Source of measured-value dis-
play
Physical dimension of display
Position of decimal point
Bus address
Adjustment of characteristic
Input of characteristic
Freely-programmable LCD
Diagnostic functions
Diagnostic functions for DS III PA and FF and P300 PA and FF
• Event counter
• Slave pointer
• Maintenance timer
• Simulation functions
• Display of zero correction
• Limit transmitter
• Saturation alarm
Physical dimensions available for the display
Physical variable
Pressure (setting can also be
made in the factory)
Level (height data)
Mass
Volume
Temperature
Miscellaneous
Input keys
PROFIBUS PA and
FOUNDATION
Fieldbus interface
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Physical dimensions
MPa, kPa, Pa, bar, mbar, torr, atm,
2
2
psi, g/cm
, kg/cm
, mmH
O,
2
mmH
O (4 °C), inH
O, inH
0
2
2
2
(4 °C), ftH
O (20 °C), mmHg, inHg
2
m, cm, mm, ft, in, yd
g, kg, t, lb, Ston, Lton, oz
3
3
3
3
3
m
, dm
, hl, yd
, ft
, in
, US gallon,
lmp, gallon, bushel, barrel, barrel
liquid
K, °C, °F, °R
%
Siemens FI 01 · 2009
2/51
2