SITRANS P measuring instruments for pressure
Transmitters for gage pressure for the paper industry
DS III series with PMC connection
■
Technical specifications
SITRANS P, DS III series for gage pressure with PMC connection for the paper industry
Input
2
Measured variable
Spans (infinitely adjustable) or
nominal measuring range and
max. permissible test pressure
Lower measuring limit
• Measuring cell with silicone oil filling
Upper measuring limit
Output
Output signal
• Lower limit (infinitely adjustable)
• Upper limit (infinitely adjustable)
Load
• Without HART communication
• With HART communication
Physical bus
With polarity reversal protection
Accuracy
Reference conditions
(All error data refer always refer to the set
span)
Error in measurement and fixed-point setting
(including hysteresis and repeatability)
• Linear characteristic
- r ≤ 10
- 10 < r ≤ 30
- 30 < r ≤ 100
Long-term drift (temperature change ± 30 °C
(± 54 °F))
Influence of ambient temperature
• at -10 ... +60 °C (14 ... 140 °F)
• at -40 ... -10 °C and +60 ... +85 °C
(-40 ... +14 °F and 140 ... 185 °F)
Influence of medium temperature
• Temperature difference between medium
temperature and ambient temperature
Influence of mounting position
Measured Value Resolution
2/52
Siemens FI 01 · 2009
© Siemens AG 2008
HART
Gage pressure
Span
Max. perm. test pres-
sure
0.01 ... 1 bar g
6 bar g
(0.145 ... 14.5 psi g)
(87 psi g)
0.04 ... 4 bar g
10 bar g
(0.58 ... 58 psi g)
(145 psi g)
0.16 ... 16 bar g
32 bar g
(2.32 ... 232 psi g)
(464 psi g)
100 mbar a (1.45 psi a)
100% of max. span
4 ... 20 mA
3.55 mA, factory preset to 3.84 mA
23 mA, factory preset to 20.5 mA or optionally set
to 22.0 mA
≤ (U
- 10.5 V)/0.023 A in Ω,
R
B
H
U
: Power supply in V
H
= 230 ... 500 Ω (SIMATIC PDM) or
R
B
= 230 ... 1100 Ω (HART Communicator)
R
B
-
-
To EN 60770-1
Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling,
room temperature 25 °C (77 °F) r: Span ratio (r = max. span/set span)
≤ (0.0029 ⋅ r + 0.071)%
≤ (0.0045 ⋅ r + 0.071)%
≤ (0.005 ⋅ r + 0.05)%
≤ (0.25 ⋅ r)% every 5 years
≤ (0.08 ⋅ r + 0.1)%
≤ (0.1 ⋅ r + 0.15)%/10 K
3 mbar/10 K (0.04 psi/10 K)
≤ 0.1 mbar g (0.00145 psi g) per 10° inclination
-
PROFIBUS PA or FOUNDATION Fieldbus
Nominal measuring
Max. perm. test pres-
range
sure
1 bar g
6 bar g
(14.5 psi g)
(87 psi g)
4 bar g
10 bar g
(58 psi g)
(145 psi g)
16 bar g
32 bar g
(232 psi g)
(464 psi g)
Digital PROFIBUS PA or FOUNDATION Fieldbus
signal
-
-
-
-
IEC 61158-2
Yes
≤ 0,075%
≤ 0.25% every 5 years
≤ 0,3%
≤ 0.25%/10 K
3 ⋅ 10
-5
of nominal measuring range