C80 Series Connection and Setup Manual
11 CNC CPU Initial Setup
11.1 Initializing CNC CPU Internal Data (Clearing SRAM Data)
(1) With the power OFF, set the CNC CPU module's rotary switch 1 (SW1) to "7". Then turn the power ON.
(2) When "-" is displayed on the right end of the dot matrix display, turn the power OFF.
The required time is approximately 10 seconds.
(3) Set SW1 to "C" and then turn the power ON. When "y" is displayed on the right end of the dot matrix display, turn the
power OFF.
The required time is approximately 10 seconds.
(4) Set SW1 to "O". (normal setting)
(Note) By clearing the SRAM, the CNC CPU module's Ethernet is set to the following initial values.
<The default value of CNC CPU module's Ethernet>
IP address: 192.168.200.1
Subnet mask: 255.255.255.0
Gateway: 0.0.0.0
IB-1501452-C
Rotary switch 1
(SW1)
150