4 General Specifications
Names of parts
No.
Name
(1)
POWER LED
(2)
ERR contact
*1
(3)
FG terminal
*1
(4)
LG terminal
(5)
Power input terminal
(6)
Terminal cover
(7)
Production information marking
*2
+24V terminal and 24G terminal
(8)
*1 Individually ground the FG and LG terminals with a ground resistance of 100 ohms or less.
*2 Only the R62P has these terminals.
IB-1501452-C
(1)
(8)
(6)
(7)
Indicates the operating status of the power supply module.
On: Normal operation
Off: Power-off, power failure, or hardware failure
[When mounting the module on the main base unit]
The contact turns on when the entire system operates normally. (M4 screw)
This contact turns off (opens) in the following cases:
• When the power supply module fails
• When the power is not supplied
• When a stop error (including reset) occurs in the CPU module
• When the fuse is blown
In a multiple CPU system, the contact turns off when a stop error occurs in any of the CPU
modules.
When the remote head module is mounted, this contact turns off when moderate or major
error (including reset) occurs.
[When mounting the module on the extension base unit]
The contact is off at all times.
When the module is mounted on a redundant power supply extension base unit, the
following operation is performed:
• The contact turns on when the power supply module operates normally. (M4 screw)
• This contact turns off (opens) when the power supply module fails, the power is not
supplied, or the fuse is blown.
A ground terminal connected to the shield pattern of the printed circuit board. This terminal
is a functional ground terminal. (M4 screw)
A ground terminal for the power supply input filter. This terminal is a functional ground
terminal. For AC input, the terminal has one-half the potential of the input voltage. (M4
screw)
A power input terminal for the power supply module. The power supply to be connected
differs depending on a power supply module. (M4 screw) (Refer to the specifications list.)
A protective cover for the terminal block.
Shows the production information (16 digits) of the module.
Used for a device that requires a supply of 24VDC. (M3.5 screw)
The power is supplied to a device through the external wiring.