7.
Verify or update the following:
a.
For Barometric pressure, type the value, subtracted from the
absolute pressure readings when calibrating in gauge pressure.
IMPORTANT NOTE: Barometric pressure is area dependent. Use
the correct barometric pressure for the area or the contracted
value.
b.
For Orifice diameter, type the diameter in inches.
c.
For Pipe diameter, type the pipe diameter in inches.
d.
For Temperature base (Tb), type the value as defined by the
existing contractual agreement (default is 60 °F).
Click Send.
8.
9.
Continue to the other tabs for additional configuration if needed.
IMPORTANT NOTE: The previous steps are the minimum requirements
to get a Totalflow XFC or XRC online and measuring gas. There are
many more steps depending on the site and company requirements.
5 4 | XSE RI ES G5 STA RT UP GUI DE | 21 0 60 0 1MNAA