The following steps detail the procedures for wall-mounting the XFC or XRC
by the meter run.
Materials:
 One (1) enclosure mounting kit (includes instructions, brackets, U-bolts
and fastening hardware)
 Four (4) wall fasteners (length and girth determined by technician
based on wall thickness and materials)
Wall-mount the XFC or the XRC:
1.
Inspect the installation location:
a.
Verify that the wall has sufficient strength to support the
hanging weight of the unit. For details on the enclosure weight
and specifications, refer to the user manual listed in
information.
b.
Verify that there are no obstructions to prevent opening the
enclosure door.
c.
Verify that there are no obstacles to prevent the solar panels
from charging during daylight hours (if installed.)
NOTICE – Equipment damage. Screw the mounting bolts into a wall
stud or wall support of sufficient strength to support the weight of
the XFC or XRC.
2.
Install the XFC or XRC mounting brackets on the back of the
enclosure using the pipe mount instructions supplied with the
mounting kit.
3.
Determine the appropriate mounting height for the XFC or XRC to
allow some downward slope from the XIMV and manifold to the
meter run tap valves. This allows condensate to drain back into the
pipe.
4.
Drill the upper mounting holes in the wall support.
5.
Measure the distance between the top and bottom mounting bracket
holes.
6.
Locate and drill the lower mounting holes in the wall support.
7.
Lift and align the enclosure on the wall so that the mounting bolt
holes match the pre-drilled holes.
8.
Insert the mounting bolts through the upper bracket holes and screw
in the bolts until tight.
9.
Repeat this procedure for the lower bracket.

Direct-mount installation

Follow the instructions supplied with the manifold and stabilizer
installation kits to mount the XFC directly on the meter run orifice.
Materials:
 One (1) 5-valve manifold
1 6 | XSE RI ES G5 STA RT UP GUI DE | 21 0 60 0 1MNAA