10

Configure communications

Configure and enable communication interfaces when needed:
 Before configuration, wire communication or peripheral equipment to
the serial communication (COMM) terminals. See section
ports.
 For remote or local network communication, note that enabling
Ethernet, Wi-Fi or Bluetooth will cause additional power consumption.

Configure COMM1

The XFC and XRC have standard configurations with COMM1 configured for
remote communications with a host. The port TF-Remote – COM1 is
configured to support the Totalflow Remote Protocol by default.
For additional details, click Help from the Communications Setup tab
screen for details.
Configure COMM1:
1.
Install the communication module for the required serial interface
type (RS-232 or RS-485) in the COMM1 slot on the XFC or XRC board.
Figure 10-1: XFC COMM terminals (Module in COMM1 slot shown)
2.
Wire the communication equipment according to the type of serial
interface required. See section
In the PCCU navigation tree, click Communications.
3.
On the Communication Setup tab, select COM1: TF Remote – COM 1.
4.
2 1 0 60 01M NAA | XSER IE S G5 S TART UP G UI DE | 5 5
4: Wire COMM
ports.
4: Wire COMM