This procedure uses the RESET button on the electronic board to restart the device. It causes the
device to restart using the running (warm) configuration. You must have physical access to the device
and be able to open the enclosure door and access the electronic board.
To restart with the reset button:
Open the door to the unit.
Locate the RESET button (S2 on the XFC
connector on the left-hand side of the board.
Figure 10-9: XFC
G5
Onboard RESET button
Observe the display. The LCD shows that the unit is shutting down and restarting.
IMPORTANT NOTE: If the device does not restart, press and hold the RESET button for
eight seconds.
10.4.3

Warm restart from the device loader

This procedure performs the warm restart from the 32-bit loader. The procedure can be performed
while on a local or remote Loader connection.
The procedure causes the device to restart with the running (warm) configuration.
To complete a warm restart from the device loader:
Launch PCCU.
Click the 32-Bit Loader icon in the toolbar. A message box displays.
Click Yes.
Verify or type the connection setup parameters and click Connect. The Loader screen
displays.
Click Services>Restart. Select Restart using Running (Warm) configuration from the drop-
down list.
1 0 8 | XSE RIE S G5 | 2 10 60 2 6MNAA