Figure 10-16: Terminal menu option
Type the command BOOT=COLD at the terminal prompt.
Figure 10-17: Terminal screen – cold boot
Press Enter.
10.4.9

Restart using the factory configuration

This procedure restores the device's startup configuration to its factory defaults from the 32-bit
loader. Factory defaults can include a generic base configuration or a custom configuration. Customers
can request custom configurations to address specific requirements in addition to the basic
configuration.
Restoring to factory configuration on a device already in service will cause service disruption and loss
of network connectivity.
NOTICE – Equipment damage or loss of data: A restart with factory defaults deletes all
data and previous configurations; both current startup and running configurations are lost.
Perform the procedures in section
factory defaults. Network communication parameters will be overwritten with factory
defaults as well. If this restart is triggered remotely on a network connection (not
recommended), you will lose connectivity with the device. You will need to have physical
access to the device to reconfigure.
To restore factory configuration:
Launch PCCU.
Click the 32-Bit Loader icon in the toolbar. A message box displays.
Click Yes.
Verify the connection setup information and click Connect. The Loader screen displays.
Click Services>Restart in the menu bar, and select Restart using Factory
configuration from the drop-down list.
10.1 Preserve data and configuration
before restoring