3.7.3 Monitoring System

Table 3-16 Semi-annual maintenance checklist for the monitoring system
Check
Item
Issue 01 (2019-03-05)
Method
Check Standard
Check that the
The components are clean
electrical
and free from dust.
components,
control
components,
SPDs, and
voltage
detection
boards are not
dusty.
Check that the
All components are normal
control board,
and free from signs of aging.
display panel,
T/H sensor,
and surge
protection and
voltage
detection board
are not aging
on the surface.
Check that all
Contactors work properly
contactors
and smoothly.
work properly.
Check that no
Cables are not aged.
cable has aged.
Check and
The T/H sensors are working
calibrate the
properly, and the
T/H sensor.
temperature and humidity
deviations are within the
allowed range.
Check whether
The water sensor cable is
the water
securely connected.
detector cable
is securely
connected.
Operation
Check Standard
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Troubleshooting
(Perform the operation with
the power off.) Use a brush
or compressed dry air to
remove dust from electrical
components, control
components, and voltage
detection boards.
Replace the abnormal board.
Replace abnormal
components.
Replace aged cables.
If the temperature error is
greater than 1° C or humidity
error is greater than 5%, the
T/H sensor must be
calibrated or replaced. For
the calibration method, see
the ACC Precision Air
Conditioner Controller User
Manual.
Connect the cable properly.
Troubleshooting
36