FusionModule1000A40 ICT Solution
Maintenance Guide
Device
VESDA
VESDA
power
supply

3.7.5 Fire Extinguishing System (CE)

Issue 01 (2019-03-05)
Operation
Check the VESDA
sampling pipes.
Remove or block a
sampling pipe.
Release smoke to
the furthest end of
a VESDA
sampling pipe.
Check the VESDA
operation panel.
Check whether the
backup power is
working properly,
and whether the
VESDA restarts
normally after the
mains powered is
disconnected.
Check the power
indicator.
Copyright © Huawei Technologies Co., Ltd.
Check
Troubleshooting
Standard
The supports
Replace damaged sampling pipes,
and connectors
and apply glue where pipes are not
of the
well sealed.
sampling pipes
are securely
connected.
An alarm is
See documents delivered with the
generated.
VESDA.
The VESDA
See documents delivered with the
generates an
VESDA.
alarm in 120s.
The VESDA
See documents delivered with the
panel displays
VESDA.
an alarm.
All indicators
See documents delivered with the
are normal.
VESDA.
The backup
See documents delivered with the
power is
VESDA.
working
properly, and
the VESDA
restarts
normally after
the mains
power is
disconnected.
1. Check the power cables.
The power
indicator turns
2. Replace by following
on.
instructions in 4.4.3 Replacing
Batteries for the VESDA Power
Box.