FusionModule1000A40 ICT Solution
Maintenance Guide
Figure 4-1 Removing screws at the upper and lower sides of the rPDU
Step 6 Lift the faulty rPDU and take it out.
Step 7 Remove the support and screws from the faulty rPDU and install them on a new rPDU.
Step 8 Mount the new rPDU with a support into the cabinet, and tighten the fastening screws of the
rPDU using a Phillips screwdriver, as shown in Figure 4-2.
Figure 4-2 Installing screws at the upper and lower sides of the rPDU
Step 9 Connect the rPDU power cable on the top of the cabinet.
Step 10 Switch on the circuit breaker for the rPDU in the PDC and check that the new rPDU is
working properly.
Step 11 Insert device power plugs in the rPDU.
Step 12 Reinstall the cabinet top baffle plate.
----End
Issue 01 (2019-03-05)
Copyright © Huawei Technologies Co., Ltd.
4 Parts Replacement
49