Table 3-6 Monthly maintenance checklist for the monitoring system
Check
Item
AC
actuator
Issue 01 (2019-03-05)
Operation
Check Standard
RF_Z
On: No network
indicator
parameters exist. A
network is waiting
to be created.
Blinking slowly: A
network is set up,
and node access is
not allowed (the
indicator blinks at
0.5 Hz, on for 1s
and then off for 1s).
Blinking at super
short intervals: A
network is set up,
and node access is
allowed (the
indicator blinks at
10 Hz, on for 0.05s
and then off for
0.05s).
Blinking at super
short intervals
intermittently: The
device is searching
for a network (the
indicator blinks at 2
Hz, on for 0.5 and
then off for 0.5s).
Operation
Check Standard
Power input
Input voltage:
90–240 V AC
Power output
Output voltage:
90–240 V AC
PWR
Steady on: The
indicator
power supply is
normal.
Off: No power
supply is available.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Troubleshooting
Refer to ECC800 Data Center
Controller V100R001C30 User
Manual to register the device, or
contact Huawei technical support.
Troubleshooting
Check the input power cables if the
input voltage is abnormal.
For details, contact Huawei technical
support.
Check the input power cables.