Toshiba V Series User Manual page 109

Integrated controller, loop controller
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

LED
STN
ONL
SCAN
Mode
Online
Offline
Standby
Rundown OFF
LED
RUN
Unit board
operation status
ALM
Module failure
LP01/LP03 output will be kept in a hold state if a transmission error occurs.
6F8C1005
Table 4-3 S20LP Indicators
Indication
Station hardware status
Operation status
(redundancy)
Scan status
Table 4-4 Station Mode Indications by S-20LP LED indicators
STN
ONL
SCAN
ON
ON
ON
OFF
ON
OFF
OFF
ON
Blinking OFF
Blinking Blinking Station address setting error
(Simultaneous
blink)
Blinking OFF
Blinking Blinking Watchdog error
(Alternative
blinking)
Table 4-5 LP01/LP02/LP03/LP04 LED Indications
Indication
ON Conditions
ON
Normal
OFF
Module failure
(ROM/RAM error)
ON
Initializing
Blinking ADC error
MV readback error
(LP01/LP03 only)
24V power drop
OFF
Normal
4.1 Indications of Operation Status LEDs
ON Conditions
ON
Normal
OFF
Self-diagnosis error upon power-on
Too frequent interruptions
Station program out of control
Station address setting error
ON
Online (system online)
OFF
Offline (standby)/Rundown
ON
Scan transmission
OFF
No scan transmission
Remarks
Scan transmission enabled
Scan transmission disabled
1. Transmission information is not stored on EEPROM at
start
2. Standby start is specified in transmission information.
3. CPU (L1PU11H) board error
Java timeout
Turn power back on to restart the
system. If it fails to restart normally,
replace the LP01/LP02/LP03/LP04
module and restart the system.
Turn power back on to restart the
system. If it fails to restart normally,
replace the LP01/LP02/LP03/LP04
module and restart the system.
Supply 24 VDC to the LP01/LP02/
LP03/LP04 module.
Remedy
Remedy