Lp04 Hardware Specifications - Toshiba V Series User Manual

Integrated controller, loop controller
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

Appendix A Table of Specifications
A.7 LP04 Hardware Specifications
A
114
Table A-18 LP04 Hardware Specifications
Item
Input
Analog input
Digital input
Output
Operation output (LP04)
Analog output
Digital output
IOBUS
Physical layer
Transmission rate
Communication
Transmission distance
Front panel
RUN LED (green)
ALM LED (red)
Rotary switch
Retentive power interruption
Insulation resistance
Withstand voltage
Power supply
LP02 unit
DI/DO
Current
LP02 unit
consumption
DI/DO
Rush current
LP02 swap
Operating
Operating temperature
environment
Humidity
Storage temperature
Installation
Weight
LP02 unit
Terminal block
External dimensions
External connection
Environmental
Power supply voltage
conditions for
Ambient temperature
accuracy
1 to 5 VDC at 4 points
Accuracy: ± 0.2%
Input resistance; 1 MΩ or higher (including the resistance at
power off)
Input break detecting function: Down scale
No-voltage contacts: 3 points
Input current: 5 mA (External power supply 24 VDC, contact
resistance 0 Ω)
Contact resistance: ON 200 Ω or less
OFF 100 KΩ or higher
Remote/manual: 1 point
Same specifications as above
Pulse width output (Open/close) 1 pair
Capacity: 30 VDC or less, 0.1 A or less (resistance load)
Pulse width; 9 ms (or 72 ms) × N seconds/control cycle
(where, N is 255 or smaller)
1 to 5 VDC at 2 points
Load resistance: 5 kΩ or higher
Accuracy ± 0.2%
FET open drain output at 3 points
Load resistance: Max. 100 mA (resistance load)
Rated voltage: 24 VDC
RS-485 1 point
19.2 Kbps
Half-duplex, asynchronous, multi-drop
Max. 100m (twisted pair, shielded cable)
ON
Operating normally
OFF
WDT triggered, ROM/RAM error, 24V power drop
ON
Initializing
OFF
Operating normally
I/O address (0 to F)
1ms (reference value)
As measured with a 500 VDC megger
100 MΩ or higher (between input and power supply)
100 MΩ or higher (between input and FG)
100 MΩ or higher (between output and FG)
500 Vrms, 1 minute (between input and power supply)
500 Vrms, 1 minute (between input and FG)
500 Vrms, 1 minute (between output and FG)
24 VDC + 10%, -15% (supplied from power unit terminal)
24 VDC + 10%, -15% (supplied from the terminal block of this
unit)
About 150 mA (at 24 VDC)
About 40 mA
Max. 5Ap-p
Hot swap possible
o
0 to 55
C
10 to 90%RH (with no condensation)
o
-25 to 70
C
Mounting on DIN rails 35 mm wide (Depth of DIN rail: 15 mm or
more)
About 220 g
About 220 g
160H × 60W × 110D
M3 screw terminal (12P × 2)
24.0V
o
25
C
model 1000 Loop Controller L1 User's Manual - Basic Hardware
Specifications

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

V10001000

Table of Contents