Advertisement

5 USER GUIDE
[Program structure]
The program structure is shown below. With the module having the node number 1
(FL.NET module for CPU01 or LPU/CMU01) and the module having the node number 2
(FL.NET module for CPU02 or LPU/CMU02) interconnected, cyclic transfer operations are
performed between the FL-net modules. (The FL.NET modules perform cyclic transfer
operations. The user does not have to pay attention to the operations.)
Subsequently, the node 1 module transmits a 1024-byte transparent message (TCD number =
11000) to the node 2 module. The node 2 module receives the transparent message from
node 1. This program example operates in this manner.
When running this user program, be sure to start it from CPU01 or LPU/CMU01.
CPU01 or LPU/CMU01
User program
Transparent
transmission
buffer
FL.NET (node 1)
module
C mode handler
Item
Function
Transmission buffer
Reception buffer
C mode handler starting
address
Node 1
Node 2
transmission
reception
area
area
CPU, LPU/CMU
Transparent message transmission.
Address
0x1E6000
Number of bytes
1024
Address
Number of bytes
toukaread( )
0xD74178
toukasend( )
0xD7417E
Node 1
reception
area
Cyclic transfer
Message transfer
CPU01
LPU/CMU01
0x450000
1024
⎯⎯
⎯⎯
0xD60160
0xD60180
5-102
CPU02 or LPU/CMU02
User program
Node 2
Transparent
transmission
reception
area
buffer
FL.NET (node 2)
module
C mode handler
CPU02
Transparent message reception.
⎯⎯
⎯⎯
0x1E6000
1024
0xD74178
0xD7417E
LPU/CMU02
0x450000
1024
0xD60160
0xD60180