[Program structure]
The program structure is shown below. With the module having the node number 1
(FL.NET module for CPU01 or LPU01) and the module having the node number 2 (FL.NET
module for CPU02 or LPU02) interconnected, cyclic transfer operations are performed
between the FL.NET modules. (The FL.NET modules perform cyclic transfer operations.
The user does not have to pay attention to the operations.)
When R0A0 startup is detected in CPU01 side ladder program subsequently, the node 1
module transmits a 1024-byte transparent message (TCD number = 11000) to the node 2
module. The node 2 module receives the transparent message from node 1 module. This
program example is a ladder program, which runs in this manner.
When using this ladder program, be sure to place the S10mini or S10V in the RUN state.
CPU01 or LPU01
Ladder program
Transparent
transmission
buffer
FL.NET (node 1)
module
Mathematical/logical
function
Item
Function
Send buffer
Receive buffer
Mathematical/logical function
Node 1
Node 2
transmission
reception
area
area
Cyclic transfer
Message transfer
CPU, LPU
Transmits transparent messages.
Address
FW000 to FW1FF
Number of bytes
1024 bytes
Address
Number of bytes
FLCM
0xD74100
Node 1
reception
area
CPU01
LPU01
⎯⎯
⎯⎯
0xD60000
5-109
5 USER GUIDE
CPU02 or LPU02
Ladder program
Node 2
Transparent
transmission
reception
area
buffer
FL.NET (node 2)
module
Mathematical/logical
function
CPU02
Receives transparent messages.
⎯⎯
⎯⎯
FW000 to FW203
1024 bytes + 4 words
0xD74100
0xD60000
LPU02