5 USER GUIDE
AST RW090 = FL404
The error code storage address (RW090 real address) is specified.
AST FW000 = FL406
The reception buffer address (FW000 real address) is specified.
DST 1024 = FL408 (MOV 1024 = FL408 for the S10V)
The reception word count is specified.
FLCM HE2800 (FLCM FW400 for the S10V)
The parameter storage address (HE2800 = FW400 real address) is specified for the
mathematical/logical function (FLCM). A message request (transparent-message
transmission) is issued to the FL.NET module.
Note: The ladder program examples presented here are created to facilitate understanding.
In a practical program, it is necessary to check an error code that is written at an error
code storage address after a "user request processing in progress" bit is reset
subsequently to message issuance.