Mitsubishi Electric MELSEC iQ-R Series User Manual page 109

Melsecnet/h network module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Item
Link Information
Mode
F Loop Status
Loopback Station
R Loopback Status
Loopback Station
Link Scan Time
Communication
Communication Status
Information
Monitor status
[Stop Monitoring] button
[Start Monitoring] button
[Error History Monitor] button
[Circuit Monitor Details] button
[Other Station Info] button
Network
[Network Test] button
Diagnostics
[Loop Test] button
[Setting Check Test] button
[Station Order Check Test]
button
[Communication Test] button
Description
Indicates the own station operation mode.
Indicates the loopback status and the station number of
the loopback station on the forward loop side.
Indicates the loopback status and the station number of
the loopback station on the reverse loop side.
Indicates the maximum/minimum/current value of the
own station link scan time.
Indicates the own station communication status.
Indicates the monitor status.
Stops/starts monitoring.
Opens the "Error History Monitor" window.
Opens the "Circuit Monitor Details" window.
Opens the "Other Station Information" window.
Opens the "Network Test" window.
Opens the "Loop Test" window.
Opens the "Setting Check Test" window.
Opens the "Station Order Check Test" window.
Opens the "Communication Test" window.
Displayed information
• Online
• Offline
• Forward Loop Test
• Reverse Loop Test
• Test between Master Station
• Test between Slave Station
• Self-loopback Test
• Internal Self-loopback Test
• Hardware test
■Loopback status
• Normal
• Loopback Transmission
• Data Link not Possible
■Loopback station number
1 to 64
• Max.
• Min.
• Current
• Normal
• There is a stop instruction (Station Own)/
Stop Instruction Present(1)
• No Parameter
• Error Parameter
• Error Host PLC
• Suspend Communication
Page 113 Error History Monitor
Page 111 Circuit Monitor Details
Page 109 Other Station Information
Page 120 Network Test
Page 116 Loop Test
Page 117 Setting Check Test
Page 118 Station Order Check Test
Page 119 Communication Test
4 TROUBLESHOOTING
4.3 Checking the Network Status
4
107

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rj71lp21-25

Table of Contents