Error code
Error details and causes
FD43H
A timeout error (send) has occurred
during the execution of the station-to-
station test and self-loopback test.
FD44H
Error reception has occurred during the
execution of the station-to-station test
and self-loopback test.
FD45H
A parity error has occurred during the
execution of the station-to-station test
and self-loopback test.
FD46H
A timeout error (receive) has occurred
during the execution of the station-to-
station test and self-loopback test.
FD47H
A reception error other than an overrun
error has occurred during the execution
of the station-to-station test and self-
loopback test.
FD48H
An overrun error (normal frame) has
occurred during the execution of the
station-to-station test and self-loopback
test.
FD49H
An overrun error has occurred during
the execution of the station-to-station
test and self-loopback test.
FD4AH
A short frame error or a reception error
of 2K bytes or more has occurred
during the execution of the station-to-
station test and self-loopback test.
FD4BH
A data error has occurred during the
execution of the station-to-station test
and self-loopback test.
*1
FE20H
The transient data received from the
MELSECNET/10 is faulty.
*1
FE21H
The start number and the number of
access points for the access target
device specified by ZNRD/ZNWR are
incorrectly set.
*1
FE22H
An access to another station was
executed with the project type different
from the actual CPU module.
*1
FE23H
Hardware failure has occurred at the
start of the dedicated instruction and
MC protocol.
FE24H
An error has occurred in the CPU
module of the target station and relay
station.
*1
FE25H
Power supply error has occurred in the
target station and relay station.
*1
FE26H
An error has occurred in the CPU
module of the target station and relay
station.
*1
FE27H
The hardware of the CPU module or
network module has failed.
*1
FE28H
The hardware of the target transient
transmission station or the network
module of the own station has failed.
FE30H to
The hardware of the network module
*1
FE32H
has failed.
*1
FE34H
The hardware of the network module
has failed.
FE36H to
The hardware of the network module
*1
FE38H
has failed.
4 TROUBLESHOOTING
138
4.5 List of Error Codes
Action
No action is required because the system performs a retry.
However, if the error occurs frequently, check for cable failure, hardware
failure, noise, and wiring error.
No action is required because the system performs a retry.
However, if the error occurs frequently, check for cable failure, hardware
failure, noise, and wiring error.
No action is required because the system performs a retry.
However, if the error occurs frequently, check for cable failure, hardware
failure, noise, and wiring error.
No action is required because the system performs a retry.
However, if the error occurs frequently, check for cable failure, hardware
failure, noise, and wiring error.
No action is required because the system performs a retry.
However, if the error occurs frequently, check for cable failure, hardware
failure, noise, and wiring error.
No action is required because the system performs a retry.
However, if the error occurs frequently, check for cable failure, hardware
failure, noise, and wiring error.
No action is required because the system performs a retry.
However, if the error occurs frequently, check for cable failure, hardware
failure, noise, and wiring error.
No action is required because the system performs a retry.
However, if the error occurs frequently, check for cable failure, hardware
failure, noise, and wiring error.
No action is required because the system performs a retry.
However, if the error occurs frequently, check for cable failure, hardware
failure, noise, and wiring error.
Correct the routing parameter or change the relay CPU module to the one
supporting the MELSECNET/10, such as AnUCPU or QnACPU.
Correct the range of the access target device of the ZNRD/ZNWR
instructions to be sent to ACPU.
With the engineering tool, check if an access to another station was
executed in the CPU module with a different project type.
Please consult your local Mitsubishi representative.
Check the status of the CPU module of the target station and relay station.
Or, change the corresponding CPU module.
Check the power supply status of the transient transmission target station
and relay station. (Check for voltage shortage, momentary power failure,
and overvoltage.) Or, change the corresponding CPU module.
Check the operating status (such as a watchdog timer error) of the CPU
module of the target station and relay station. Or, change the
corresponding CPU module.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Detailed
Information

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rj71lp21-25

Table of Contents