Mitsubishi Electric MELSEC iQ-R Series User Manual page 128

Melsecnet/h network module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error code
Error details and causes
3006H
Pairing is not set to the stations in a
redundant system.
3007H
Pairing is set to the stations not
included in a redundant system.
3008H
"RJ71LP21-25" is selected for the
module name in a redundant system.
"RJ71LP21-25(R)" is selected for the
module name in a system other than a
redundant system.
3040H
Response data of the dedicated
instruction cannot be created.
3C00H to 3C02H
A hardware failure has been detected.
3C0FH
A hardware failure has been detected.
3C10H
A hardware failure has been detected.
3C14H
A hardware failure has been detected.
3C2FH
An error was detected in the memory.
3E00H
An error was detected in the network
module.
3E01H
Network type of the own station is
unexpected setting.
F007H to F008H
An error was detected in the network
module.
F013H
The network parameter setting is
incorrect.
F101H to F102H
The network is booting.
F103H
Online test is being executed.
4 TROUBLESHOOTING
126
4.5 List of Error Codes
Action
Check the pairing setting in "Network Range Assignment" of "Required
Settings" of the control station.
Check the pairing setting in "Network Range Assignment" of "Required
Settings" of the control station.
When using the module in a redundant system, select "RJ71LP21-25(R)"
for the module model name in the "Add New Module" window.
When using the module in a system other than a redundant system, select
"RJ71LP21-25" for the module model name in the "Add New Module"
window.
• Increase the request interval.
• Decrease the number of request stations.
• Wait for a response to the previous request before sending the next
request.
• Correct the timeout value.
• Take measures to reduce noise.
• After the CPU module is reset, switch to RUN. If the error occurs again
even after taking the above, the possible cause is a hardware failure of
the module, base unit, or extension cable. Please consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• After the CPU module is reset, switch to RUN. If the error occurs again
even after taking the above, the possible cause is a hardware failure of
the module, base unit, or extension cable. Please consult your local
Mitsubishi representative.
• Take measures to reduce noise.
• After the CPU module is reset, switch to RUN. If the error occurs again
even after taking the above, the possible cause is a hardware failure of
the module, base unit, or extension cable. Please consult your local
Mitsubishi representative.
After the CPU module is reset, switch to RUN. If the error occurs again
even after taking the above, the possible cause is a hardware failure of the
error module or CPU module. Please consult your local Mitsubishi
representative.
After the CPU module is reset, switch to RUN. If the error occurs again
even after taking the above, the possible cause is a hardware failure of the
error module. Please consult your local Mitsubishi representative.
After the CPU module is reset, switch to RUN. If the error occurs again
even after taking the above, the possible cause is a hardware failure of the
error module. Please consult your local Mitsubishi representative.
Rewrite the module parameter using the engineering tool. If the error
occurs again even after taking the above, the possible cause is a
hardware failure of the error module. Please consult your local Mitsubishi
representative.
Please consult your local Mitsubishi representative.
• Correct the network parameter setting and write data to the
programmable controller.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
Wait until 'Baton pass error status of own station' (SB0047) and 'Data link
error status of own station' (SB0049) go back to normal.
Wait until 'Baton pass error status of own station' (SB0047) and 'Data link
error status of own station' (SB0049) go back to normal.
Detailed
Information
Parameter
information
• Parameter type
• I/O No.
• Parameter No.
• Network No.
• Station No.
Parameter
information
• Parameter type
• I/O No.
• Parameter No.
• Network No.
• Station No.
Parameter
information
• Parameter type
• I/O No.
• Parameter No.
• Network No.
• Station No.